Skip to main content

A Comprehensive Analysis of Touch and Step Voltage Hazards in High-Voltage Grounding Systems

 

A Comprehensive Analysis of Touch and Step Voltage Hazards in High-Voltage Grounding Systems


The Physics of Ground Potential Rise (GPR)

The safety of personnel and the public in and around high-voltage electrical installations, such as substations and transmission towers, is a paramount concern in power system engineering. During a ground fault condition, the electrical potential of the grounding system and the surrounding earth can rise to hazardous levels. This phenomenon, known as Ground Potential Rise (GPR), is the root cause of two distinct but related electrical shock hazards: touch voltage and step voltage. Understanding the physics of GPR is the essential first step in analyzing, quantifying, and ultimately mitigating these dangers. The entire framework of grounding safety is built upon managing the consequences of this initial event, which transforms the earth itself into a component of a dangerous electrical circuit.








The Ground Fault Event: From Short Circuit to Earth Injection

A ground fault is an unintentional, low-impedance connection between an energized conductor and the earth or a grounded structure. Such events can be initiated by various causes, including lightning strikes, equipment insulation failure, or a physical breach of an energized line, such as a conductor falling to the ground or onto a metallic object like a vehicle or fence. When this occurs, the electrical system's protective grounding grid is called upon to perform its primary function: to provide a safe and effective path for the resulting fault current to flow into the general mass of the earth.

This massive injection of current, which can be thousands of amperes, does not simply vanish. In accordance with fundamental circuit principles, the current must complete a circuit by returning to its source, which is typically the neutral of a transformer or generator, itself connected to earth. The earth, therefore, becomes a part of the fault circuit. The magnitude of this fault current is a primary determinant of the severity of the resulting electrical hazard; the more current that is injected into the ground, the greater the potential danger. The grounding system, while designed to contain and control this fault current, paradoxically becomes the source of the very hazards it is intended to mitigate. The act of safely channeling fault current into the earth is what creates the GPR, which in turn generates the dangerous voltage gradients. This is not a design failure but an inherent characteristic of grounding systems that necessitates a comprehensive approach to safety engineering, focusing not on the elimination of GPR but on the meticulous control of the potential differences it creates.








Ground Potential Rise (GPR) Explained: The Zero-Reference Problem

The earth is not a perfect conductor; it possesses a finite, measurable resistance to the flow of electrical current. When the fault current (I_g) flows through the resistance of the grounding grid (R_g), it produces a voltage rise according to Ohm's Law. This voltage is defined as the Ground Potential Rise (GPR), the maximum voltage that a grounding system achieves with respect to a distant point on the earth assumed to be at zero potential. The relationship is expressed as:

This GPR elevates the electrical potential of the entire grounding grid—and, critically, all metallic structures conductively bonded to it—to a value that can be many kilovolts above true earth potential. This includes substation equipment casings, steel support structures, transmission tower legs, metal fences, and control cabinets. A person standing within the substation is therefore in an environment where the ground beneath their feet and the equipment around them are at a dangerously high voltage relative to a safe, remote location. However, the immediate danger is not the absolute voltage itself, but the potential differences that arise within this energized zone.







The Voltage Gradient: Visualizing the Hazard Zone

The GPR is highest at the point of fault current injection and at the grounding system itself. As the current dissipates through the soil away from the injection point, this voltage gradually decreases. This phenomenon can be visualized as ripples spreading from a stone dropped into a pond; the ripples are highest at the center and diminish with distance. This spatial variation in voltage across the earth's surface is known as the voltage gradient.

The voltage does not decrease linearly with distance. Instead, the gradient is typically steepest close to the grounding system and becomes progressively flatter further away. This means that the voltage drop over a one-meter distance is much greater near the fault than it is 50 meters away. It is this voltage gradient that creates the potential differences responsible for both touch and step voltage hazards. A person walking across this gradient will experience a difference in potential between their feet, and a person touching a grounded structure will experience a difference in potential between their hand and their feet. The shape and steepness of this gradient are dictated almost entirely by the electrical properties of the soil.








The Critical Role of Soil Resistivity

Soil resistivity is the single most important parameter governing the performance of a grounding system and the magnitude of touch and step voltage hazards. It is a measure of the soil's inherent resistance to the flow of electrical current, typically expressed in ohm-meters (\Omega \cdot m). Unlike a metallic conductor with a well-defined resistance, soil is a highly variable and complex medium. Its resistivity is influenced by a multitude of factors, including its composition (clay, sand, rock), moisture content, temperature, and the concentration of dissolved electrolytes and minerals. Dry, rocky, or sandy soil generally exhibits high resistivity, while moist, clay-like soil has lower resistivity.

For grounding system analysis, assuming a simple, uniform soil model can be dangerously inaccurate. In reality, soil is almost always stratified into multiple layers, each with a different resistivity. The behavior of fault current and the resulting surface voltage gradients are profoundly affected by this layering. For instance, a common and particularly hazardous scenario involves a high-resistivity top layer (such as dry gravel or sandy topsoil) overlying a more conductive, low-resistivity bottom layer (such as wet clay). In this case, the fault current injected into the surface layer will preferentially flow downward into the path of least resistance offered by the lower layer. This vertical current flow through the high-resistivity top layer causes a very large voltage drop over a short distance. This steep vertical voltage drop manifests as an exceptionally steep horizontal voltage gradient on the surface near the electrode, leading to much higher step voltages than would be predicted by a uniform soil model. This non-intuitive effect underscores the deceptive nature of soil and highlights why accurate, site-specific soil resistivity measurements and sophisticated multi-layer modeling are not just best practices, but are absolutely essential for a safe and effective grounding system design.








Defining and Differentiating Touch and Step Voltage

Arising from the voltage gradients created by a Ground Potential Rise event, touch and step voltages represent the two primary electrical shock scenarios that endanger individuals near high-voltage facilities during a fault. While both originate from the same physical phenomenon, they are distinct in their mechanics, the path the current takes through the human body, and their relative level of danger. A precise understanding of each is fundamental to the design of effective safety measures. The core principle underlying both hazards is that danger arises not from being in a high-voltage environment, but from simultaneously contacting two points that are at different potentials, thereby allowing the human body to complete an electrical circuit. Safety engineering, therefore, is the practice of managing and minimizing these potential differences to survivable levels.

Touch Voltage: The Hand-to-Foot Hazard

Touch voltage (E_t) is defined as the potential difference between the Ground Potential Rise (GPR) of a grounded structure that a person is touching and the surface potential of the earth at the point where the person is standing.

During a ground fault, a metallic object bonded to the grounding grid, such as a transformer casing or a substation fence, becomes energized to the full GPR potential. A person standing on the nearby soil, which is at a lower potential due to the voltage gradient, creates a hazardous potential difference by touching the object. This voltage drives a current through the person's body, forming a dangerous electrical circuit. The current path begins at the hand touching the equipment, travels through the arm and across the torso—critically passing through the region of the heart and lungs—then proceeds down the legs, exits through the feet into the earth, and returns to the grounding system to complete the circuit.

For example, consider a fault that causes a substation GPR of 5000 V. A person touches a steel support column, which is at 5000 V. The soil one meter away, where their feet are, might be at a potential of 4000 V due to the voltage gradient. The touch voltage experienced by this person is the difference between these two potentials: 5000 \, V - 4000 \, V = 1000 \, V. For the purposes of standardized calculation and analysis, engineering standards like IEEE Std 80 typically assume a horizontal reach distance of 1 meter from the energized object to the person's feet.

Step Voltage: The Foot-to-Foot Hazard

Step voltage (E_s) is defined as the difference in surface potential experienced by a person bridging a distance of 1 meter with their feet, without contacting any other grounded object.

This hazard occurs when an individual walks or stands within the voltage gradient field. Because the ground potential changes with distance from the fault, a person's two feet, separated by the length of a stride, will be resting on points of different voltage. This potential difference will drive a current through the body. The circuit path for step voltage is from the foot at the higher potential, up that leg, across the lower abdomen and pelvic area, and down the other leg to the foot at the lower potential.

For instance, if a person is walking near a downed power line, one foot might land on a point where the surface potential is 900 V, while the other foot, taking a standard 1-meter step, lands on a point with a potential of 800 V. The step voltage across the person's lower body would be 100 V. To ensure safety and consistency in design calculations, the standard distance for a step is defined as 1 meter. If a person keeps their feet together, they are at a single point on the voltage gradient, the potential difference across their body is zero, and no current will flow. This is the basis for the safety recommendation to shuffle or hop with feet together when evacuating an area with a potential step voltage hazard.

Comparative Analysis of Hazards

Although both touch and step voltage stem from the GPR, their characteristics and the dangers they pose are significantly different. The primary distinction lies in the path that the electrical current takes through the body.

In a touch voltage scenario, the current path is typically hand-to-feet. This route traverses the chest cavity, directly involving the heart and respiratory muscles. Consequently, touch voltage is generally considered the more severe hazard, as it carries a much higher risk of inducing ventricular fibrillation—the primary cause of death from electric shock—even at lower current levels.

In a step voltage scenario, the current path is foot-to-foot, confined to the lower body. This path largely bypasses the heart and other vital organs in the torso. While a step voltage shock can cause severe pain, involuntary muscle contractions, and deep burns, the direct risk of cardiac arrest is lower. However, this does not render step voltage safe. A severe shock can cause a person to lose their balance and fall to the ground. This fall can create a new and far more dangerous shock scenario, such as a hand-to-foot or head-to-feet contact, which could be fatal. Furthermore, automatic reclosing devices on power lines may re-energize a faulted line seconds after the initial event, potentially delivering a second shock to a victim who has fallen and is unable to move.

The following table provides a side-by-side comparison of these two hazards.

Table 2.1: Comparative Analysis of Touch vs. Step Voltage

Feature

Touch Voltage

Step Voltage

Definition

The potential difference between an energized, grounded object and the feet of a person in contact with that object.

The potential difference between the feet of a person bridging a distance of 1 meter across a voltage gradient.

Points of Contact

Hand(s) to Feet.

Foot to Foot.

Current Path

Through arms, torso (including heart and lungs), and legs.

Through legs and pelvic region, largely bypassing the torso.

Primary Physiological Risk

High probability of ventricular fibrillation due to current path through the heart.

Muscle contraction, severe burns, and falls leading to secondary, more dangerous contact.

Standard Distance

1-meter reach from the object to the feet.

1-meter stride between the feet.

Typical Scenario

Touching a substation transformer casing, fence, or tower leg during a ground fault.

Walking or standing near a downed power line or in a substation yard during a ground fault.

The Special Case of Transferred Voltage: The Remote Hazard

Transferred voltage is a particularly insidious and often the most dangerous form of touch voltage hazard. It is defined as a touch voltage scenario where a voltage, often approaching the full GPR of a substation, is transferred via a metallic conductor from inside the GPR zone to a remote point outside of this zone.

This occurs when conductive objects such as metal fences, pipelines, communication cables, or railway tracks are bonded to the substation grounding grid and extend far beyond the immediate area of the substation. During a fault, these conductors become energized to the full GPR potential and carry this high voltage to distant locations. A person standing at one of these remote locations, who is on soil at or near true zero potential, may touch the energized conductor. In this case, the person bridges the entire potential difference between the GPR and remote earth. The resulting touch voltage can be nearly equal to the full GPR, which can be an order of magnitude higher than the touch voltages experienced within the substation itself, where the local soil potential is also elevated, thereby reducing the net potential difference.

This phenomenon reveals a critical limitation in safety analyses that are confined only to the immediate substation area. The conductive footprint of a facility can extend for miles, exporting a lethal hazard to unsuspecting individuals in public spaces. A grounding design that is perfectly safe within the substation fence can create an extremely dangerous condition elsewhere. This necessitates a broader, system-wide analysis that traces all conductive paths leaving a high-voltage site to identify and mitigate these remote, transferred voltage risks.

The Physiological Impact of Electrical Shock

The ultimate purpose of grounding system design is to protect human life. To do this effectively, engineers must understand not only the physics of electricity but also the physiological effects of electrical current on the human body. The danger of touch and step voltage is not the voltage itself, but the current that this voltage drives through the body. The magnitude, duration, and path of this current determine the severity of the injury, ranging from a mild tingling sensation to immediate death.

The Human Body as a Conductor: Impedance and Its Variables

The human body, composed of approximately 70% water containing dissolved electrolytes, is an effective conductor of electricity. Tissues and fluids with high electrolyte content, such as blood, nerves, and muscles, offer low resistance to current flow. In contrast, tissues like bone, fat, and skin have higher resistance. For the purpose of safety calculations, the total opposition to current flow is termed impedance, which for alternating current (AC) includes both resistance and reactance. In many practical standards, this is simplified to resistance.

The single largest component of the body's impedance is the skin. Under dry conditions, the outer layer of skin (stratum corneum) can have a resistance as high as 100,000 \Omega, providing a significant degree of natural protection. However, this resistance is highly variable and unreliable. Moisture from sweat, water, or wet conditions can dramatically lower skin resistance to 1,000 \Omega or less. Similarly, any break in the skin, such as a cut or abrasion, effectively bypasses this protective layer.

A critical phenomenon occurs at higher voltages (typically above 500–600 V), known as dielectric breakdown of the skin. At these potentials, the skin's insulating properties are punctured, and its resistance plummets, reducing the overall body impedance to as low as 500 \Omega. This presents a dual threat: not only is the driving voltage higher in high-voltage incidents, but the body's primary resistive defense is simultaneously destroyed, leading to catastrophic levels of internal current flow and severe thermal damage. For standardization in safety calculations, IEEE Std 80 conservatively assumes a constant internal body resistance of 1000 \Omega from hand-to-hand or hand-to-foot.

Current, Not Voltage: The Agent of Injury

It is a fundamental principle of electrical safety that the physiological damage from an electric shock is caused directly by the magnitude of the current flowing through the body's tissues, not by the voltage potential itself. The voltage is merely the driving force that, according to Ohm's Law (I = V/R), determines how much current will flow through the body's impedance. Even a very high voltage may be harmless if the circuit resistance is high enough to limit the current to a negligible level. Conversely, a relatively low voltage can be lethal if body resistance is low (e.g., in wet conditions).

The effects of 50 Hz or 60 Hz AC current, typical of power systems, are well-documented and escalate dramatically with increasing magnitude. The following table synthesizes data from various safety sources to illustrate these effects.

Table 3.1: Physiological Effects of 60 Hz AC Current

Current Level (mA)

Sensation/Effect

Source(s)

Below 1 mA

Generally not perceptible; faint tingle.


5 mA

Slight shock felt; not painful but disturbing and can cause involuntary reactions.


10–20 mA

"Let-Go" Threshold. Painful shock; loss of voluntary muscle control. Flexor muscles contract, causing the victim to be unable to release their grip on an energized object.


20–50 mA

Severe pain; paralysis of respiratory muscles. Breathing becomes difficult or ceases.


50–100 mA

Ventricular Fibrillation Threshold. Irregular, uncoordinated heart muscle contractions; heart stops pumping blood. Usually fatal without immediate defibrillation.


1,000–4,300 mA (1.0–4.3 A)

Ventricular fibrillation certain; muscular contraction and nerve damage occur. Death is likely.


> 10,000 mA (10 A)

Cardiac arrest (heartbeat stops completely); severe burns and organ damage. Death is probable.


A critical inflection point in this scale is the "let-go" threshold. At currents around 16 mA for an average man, involuntary contraction of the flexor muscles in the arm and hand is so strong that the victim cannot release their grasp of an energized conductor. This physiological trap transforms what might have been a brief, survivable shock into a prolonged event. Since the risk of fibrillation depends on both the magnitude and duration of the current, the inability to let go dramatically increases the likelihood of a fatal outcome, even at voltages found in ordinary households.

Ventricular Fibrillation: The Primary Lethal Threat

The most common cause of death from electric shock is ventricular fibrillation (VF). The human heart maintains its rhythmic pumping action through a series of small, precisely timed internal electrical impulses. When an external electrical current of sufficient magnitude passes through the heart, it can overwhelm and disrupt this natural pacemaker system, throwing the heart muscle into a state of rapid, chaotic, and ineffective quivering.

In this state, the heart's ventricles no longer contract coherently and cease to pump blood to the brain and other vital organs. The victim will lose consciousness within seconds. Without immediate cardiopulmonary resuscitation (CPR) and the application of a medical defibrillator to restore a normal heart rhythm, irreversible brain damage and death will occur within minutes. The threshold for VF is tragically low, beginning in the range of 50–100 mA for a shock duration of a few seconds. This vulnerability of the heart's electrical system is the central reason why the current path through the body is a critical factor in assessing the danger of a shock scenario.

Relative Dangers of Touch vs. Step Current Paths

The specific path that current takes through the body determines which organs are at risk and, therefore, the relative danger of the shock.

The touch voltage path, typically hand-to-foot or hand-to-hand, is exceptionally dangerous. This path directs the current directly through the chest cavity, placing the heart and lungs in the circuit. Because the heart is directly exposed to the current, the probability of inducing ventricular fibrillation is very high. This makes touch voltage the most critical hazard to mitigate in grounding system design.

The step voltage path, from foot to foot, is generally less hazardous with respect to immediate fatality. The current is largely confined to the legs and pelvic region, bypassing the heart and other vital organs in the torso. While a step voltage shock can cause extreme pain, violent muscle spasms, and severe burns at the entry and exit points (the feet), it is less likely to cause VF directly. However, the danger is far from negligible. The intense muscle contractions can be powerful enough to break bones or throw the victim to the ground. This fall is a critical secondary hazard. A person falling may inadvertently make contact with the ground with their hands, arms, or head, creating a new, far more lethal current path (e.g., hand-to-foot) that does pass through the heart. This risk is compounded by the presence of automatic reclosers on power systems, which can re-energize a faulted line seconds after the initial trip, delivering a second, potentially fatal shock to a victim who is already on the ground and incapacitated.

Engineering Safety Standards and Tolerable Limits

The design of safe grounding systems is not left to arbitrary rules of thumb; it is governed by rigorous engineering standards that translate the principles of physics and physiology into quantifiable safety criteria. The foremost of these in North America, and highly influential globally, is IEEE Std 80, the "IEEE Guide for Safety in AC Substation Grounding". This standard provides a comprehensive methodology for analyzing and designing grounding systems to protect personnel from hazardous touch and step voltages.

Introduction to IEEE Std 80: The Cornerstone of Grounding Safety

Historically, the primary metric for a grounding system's adequacy was its resistance to remote earth. A common guideline was to achieve a resistance of 1 \Omega or less for large transmission substations and 5 \Omega or less for distribution substations. However, experience and analysis demonstrated that a low resistance value, while generally beneficial for reducing GPR, is not in itself a guarantee of safety. Conversely, a substation with a high ground resistance is not necessarily unsafe.

This realization led to a fundamental philosophical shift in grounding design, which is embodied in modern versions of IEEE Std 80. The standard moved away from simple prescriptive resistance targets to a performance-based approach. The modern objective is not to achieve an arbitrary resistance value, but to ensure that the calculated touch and step voltages that will actually occur during a fault are below the tolerable limits that a human can safely withstand. This performance-based methodology requires a holistic analysis that integrates the characteristics of the power system, the geological properties of the site, the physical layout of the grounding grid, and the physiological tolerance of the human body. It forces a collaboration between different engineering disciplines, as the final design's safety depends on variables controlled by geotechnical engineers (soil resistivity), civil engineers (surface materials), and protection engineers (fault clearing times).

Calculating Tolerable Body Current (I_B)

The foundation of the IEEE Std 80 safety criteria is the determination of the maximum electrical current the human body can withstand without a high probability of suffering ventricular fibrillation. Based on extensive empirical research, the standard provides a formula that relates this tolerable body current (I_B) to the duration of the shock (t_s). The relationship is inverse-proportional to the square root of time, meaning the body can tolerate higher currents for shorter durations. The formula is:

Where:

  • I_B is the tolerable RMS current through the body in amperes (A).

  • t_s is the duration of the shock current in seconds (s).

  • k is an empirical constant related to the shock energy that a person of a certain body weight can tolerate. IEEE Std 80 provides two values for k:

  • k = 0.116 for a person with a body weight of 50 kg (110 lbs).

  • k = 0.157 for a person with a body weight of 70 kg (154 lbs).

The 50 kg body weight model is more conservative, as it results in a lower tolerable current, and is therefore commonly used in designs where public safety is a concern.

Deriving Tolerable Touch Voltage Limits (E_{touch})

The tolerable touch voltage is the maximum potential difference a person can safely contact between their hand and feet without the resulting body current exceeding the tolerable limit, I_B. To calculate this, IEEE Std 80 models the human body as an equivalent electrical circuit. In the touch voltage scenario, this circuit consists of the body's internal resistance (R_B) in series with the resistance of the two feet in parallel making contact with the earth (R_F/2). The total impedance of the circuit is therefore (R_B + R_F/2).

The tolerable touch voltage (E_{touch}) is simply this total impedance multiplied by the tolerable body current (I_B):

IEEE Std 80 provides a more practical formula by substituting standard values and expressing the foot resistance in terms of surface material resistivity. For a 50 kg person, the formula becomes:

Each component of this critical formula represents a key aspect of the safety analysis, as detailed in Table 4.1. The term C_s \cdot \rho_s effectively calculates the resistance of the path to ground through the person's feet, considering the insulating effect of any surface layer material like crushed rock.

Deriving Tolerable Step Voltage Limits (E_{step})

The tolerable step voltage is calculated in a similar manner. The equivalent circuit for a person in a step voltage scenario consists of the internal body resistance (R_B) in series with the resistance of two feet (each considered a separate point of contact with the earth), giving a total foot resistance of 2 \cdot R_F. The total impedance of this circuit is (R_B + 2 \cdot R_F).

The tolerable step voltage (E_{step}) is this total impedance multiplied by the tolerable body current (I_B):

Substituting the standard values for a 50 kg person, the practical formula is:

The coefficients of 1.5 for touch voltage and 6.0 for step voltage reflect the different circuit configurations for the foot resistance in each scenario. Because the foot resistance term is larger in the step voltage equation, the tolerable step voltage limit is always significantly higher than the tolerable touch voltage limit for the same site conditions.

The following table provides a glossary of the key parameters used in these essential safety calculations.

Table 4.1: Key Parameters in IEEE Std 80 Tolerable Voltage Calculations

Symbol

Parameter Name

Definition and Standard Value/Notes

E_{touch}

Tolerable Touch Voltage

The maximum voltage a person can withstand between hand and feet without fibrillation. Calculated using the relevant formula.

E_{step}

Tolerable Step Voltage

The maximum voltage a person can withstand between their feet (1 m apart) without fibrillation. Calculated using the relevant formula.

I_B

Tolerable Body Current

The maximum RMS current the body can tolerate. It is a function of shock duration and body weight.

R_B

Body Resistance

The internal resistance of the human body. Standardized as 1000 \Omega for calculations.

R_F

Foot Resistance

The resistance of a single foot to the earth. It is a function of surface resistivity and is not used directly in the final formulas.

\rho_s

Surface Material Resistivity

The resistivity of the material at the earth's surface (e.g., crushed rock, asphalt, soil), measured in \Omega \cdot m. A key variable in design.

t_s

Shock Duration / Fault Clearing Time

The time duration of the fault current, determined by primary and backup protection relay settings. Typically 0.5 s to 1.0 s is used for conservative design.

C_s

Surface Layer Derating Factor

A complex reduction factor that accounts for the insulating effect of a high-resistivity surface layer over the native soil. It depends on layer thickness and the resistivities of the layers. Varies from 1.0 (no surface layer) to lower values for effective layers.

k

Body Weight Constant

An empirical constant for the tolerable shock energy. k=0.116 for 50 kg; k=0.157 for 70 kg.

The application of a high-resistivity surface layer, such as crushed gravel, is often the most critical and cost-effective lever in achieving a safe design. In locations with poor native soil conditions, it can be prohibitively expensive to lower the GPR sufficiently. However, adding a layer of gravel significantly increases \rho_s, which in turn increases the calculated tolerable touch and step voltage limits. This allows a design to achieve safety compliance not by reducing the actual hazard voltage, but by increasing the human body's resistance to it, a strategy quantitatively supported by the IEEE Std 80 framework.

The Influence of Fault Clearing Time (t_s)

The shock duration, or fault clearing time (t_s), is a critically important variable in the safety equations. The tolerable voltage limits are inversely proportional to the square root of t_s. This means that halving the fault clearing time does not double the tolerable voltage, but increases it by a factor of \sqrt{2} (approximately 1.414). Conversely, a longer fault duration significantly reduces the level of voltage a person can safely withstand.

This relationship directly links the civil and electrical design of the grounding system to the domain of protection and control engineering. One of the most powerful mitigation strategies for a grounding system that fails to meet safety criteria is to reduce the fault clearing time by adjusting the settings of protective relays and using high-speed circuit breakers. The design must consider both the primary (fastest) protection clearing time and the backup clearing time, which is longer and results in more stringent (lower) tolerable voltage limits. The potential for automatic reclosing sequences must also be factored into the analysis, as they can expose an individual to multiple shocks.

Mitigation Strategies and Safety by Design

Ensuring personnel safety from touch and step voltage hazards requires a multi-faceted approach that begins with the fundamental design of the grounding system and extends to the implementation of administrative controls and the use of personal protective equipment (PPE). These mitigation strategies can be viewed as a hierarchy of controls, where the most effective measures are engineered solutions that passively and permanently reduce the hazard, followed by measures that create safe work zones, and finally, those that rely on individual action and equipment. A robust safety program employs a defense-in-depth strategy, integrating elements from all levels of this hierarchy.

Primary Mitigation: Grounding System Design

The most fundamental method of mitigating touch and step voltage hazards is through the careful design of the substation grounding grid itself. The primary goals are to reduce the overall GPR and to control the voltage gradients on the surface.

  • Reducing Grounding System Resistance (R_g): A lower grid resistance will result in a lower GPR for a given fault current. This is the first line of defense. Methods to reduce R_g include:

  • Increasing the Grid Area: A larger grid provides more surface area for current to dissipate into the earth, lowering the overall resistance.

  • Increasing Conductor Length: Adding more buried conductors in a mesh pattern increases the total length of conductor in contact with the soil, which reduces resistance.

  • Utilizing Ground Rods: Driving vertical ground rods, especially deep rods that can penetrate into lower-resistivity soil layers, is a highly effective way to lower the grid resistance.

  • Strategic Placement of Conductors: While reducing GPR is important, controlling the shape of the voltage gradient is equally critical for managing touch and step potentials.

  • Perimeter Conductors: A conductor buried around the full perimeter of the grounding grid, typically just inside the fence line, helps to control the voltage gradient at the boundary of the substation, reducing touch potentials for anyone contacting the fence.

  • Closer Conductor Spacing: A grid with closely spaced conductors (a smaller mesh) behaves more like a solid metallic plate. This forces the surface potential to be more uniform across the substation, smoothing out steep voltage gradients and thereby reducing both step voltages within the grid and touch voltages on equipment bonded to it. Conductors should be placed near the bases of equipment and structures where people are likely to be working.

Secondary Mitigation: Surface Layer Treatment

The application of a high-resistivity surface layer is one of the most common and effective engineering controls for mitigating touch and step voltage hazards. This typically involves spreading a layer of clean, crushed rock (gravel) or paving the area with asphalt.

The primary function of this layer is not to lower the GPR, but to increase the contact resistance between a person's feet and the underlying soil. This added series resistance in the shock circuit limits the amount of current that can flow through the body for a given touch or step voltage. The effectiveness of this method is quantified directly in the IEEE Std 80 tolerable voltage formulas through the surface material resistivity (\rho_s) and the surface layer derating factor (C_s). A thicker, more resistive layer raises the tolerable voltage limits, often making an otherwise non-compliant design safe. For this method to remain effective, the surface material must be maintained. It should be kept at its designed thickness and be free of weeds or significant soil contamination, as these can reduce its overall resistivity and compromise its protective value.

Advanced Mitigation: Gradient Control Mats

In specific, high-risk locations where personnel must stand to operate equipment (such as a disconnect switch handle), a gradient control mat may be installed to create a localized equipotential zone. A gradient control mat is a metallic grid, often made of steel or copper mesh, that is placed on or just below the surface of the ground.

The mat is conductively bonded to the frame of the equipment being operated. A person standing on the mat and touching the equipment has both their feet and their hands referenced to the same metallic grid. Even if the entire mat is elevated to a high potential during a fault, the potential difference between the person's hands and feet is minimized to a very low and safe value. This effectively shorts out the hazardous touch voltage across the body. Gradient control mats can be permanent installations buried in substations or portable versions (such as the CHANCE® Equi-mat™) used by field crews to establish temporary safe work zones. In specialized applications near cathodically protected pipelines, these mats may be connected via a solid-state decoupler, which isolates the mat from the pipeline under normal DC conditions but provides a solid bond during an AC fault, preventing interference with corrosion protection systems.

System-Level and Administrative Controls

Beyond the physical grounding system, several other strategies contribute to a comprehensive safety program.

  • Fault Current Management:

  • Limitation: In some systems, neutral grounding resistors or reactors are used to intentionally limit the maximum magnitude of current that can flow during a ground fault. This directly reduces the GPR (GPR = I_g \times R_g).

  • Diversion: The presence of overhead ground wires or metallic cable sheaths connected to the substation grid provides alternative return paths for fault current. A portion of the current will flow back through these metallic paths instead of through the earth. This "split factor" reduces the amount of current injected into the grid (I_g) and thus lowers the GPR.

  • Accelerated Fault Clearing: As established by the IEEE Std 80 formulas, reducing the fault duration (t_s) raises the tolerable voltage limits. Employing high-speed protective relaying schemes and fast-acting circuit breakers is a powerful method for improving safety.

  • Personal Protective Equipment (PPE): PPE is the last line of defense. Dielectric footwear (EH-rated boots) and insulating rubber gloves add a significant amount of resistance to the shock circuit, drastically reducing the current that can flow through the body. While highly effective, PPE relies on proper selection for the voltage level, regular inspection and testing, and consistent use by personnel.

  • Administrative Controls: These include physical barriers such as fences, warning signs, and restricted access policies to keep unauthorized and untrained individuals out of potentially hazardous areas.

Ultimately, grounding system design is an optimization problem that balances safety, cost, and practicality. In a location with highly resistive soil, achieving a very low grid resistance might be economically unfeasible. An alternative, equally safe design might accept a higher grid resistance and a correspondingly higher GPR, but mitigate the hazard by investing in a thick, high-resistivity surface layer and faster protective relaying. This systems-based approach, leveraging all available variables in the IEEE Std 80 framework, allows engineers to design a safe and reliable system tailored to the unique conditions of each site.

Conclusion

The distinction between touch and step voltage is fundamental to electrical safety in high-voltage environments. Both hazards originate from the same phenomenon—the Ground Potential Rise during a fault—but they differ critically in the mechanism of contact, the path of current through the body, and the specific physiological risks they present.

Touch voltage, the hand-to-foot hazard, is the more severe of the two due to its current path directly traversing the heart, posing a significant risk of ventricular fibrillation. Step voltage, the foot-to-foot hazard, presents a current path that largely bypasses vital organs, but remains dangerous due to the potential for severe burns and falls that can lead to more lethal secondary contacts. A special case, transferred voltage, represents the most extreme touch voltage risk, where the full GPR can be exported to remote locations via metallic conductors, creating a severe, often unanticipated, public hazard.

The analysis of these dangers is not merely qualitative. Industry standards, led by IEEE Std 80, provide a rigorous, performance-based framework for quantifying risk. This modern approach has shifted the focus from achieving arbitrary ground resistance values to a holistic design philosophy. Safety is achieved by ensuring that the actual touch and step potentials generated during a fault remain below calculated tolerable limits, which are themselves a function of human physiology, fault clearing time, and local site conditions.

Effective mitigation requires a defense-in-depth strategy. This encompasses primary engineering controls in the grounding system design to limit GPR and shape voltage gradients; secondary controls like high-resistivity surface layers to increase contact resistance; advanced solutions such as gradient control mats to create localized equipotential zones; and system-level controls including fault current limitation and accelerated protection schemes. These engineered solutions are supplemented by administrative controls and the critical final layer of personal protective equipment.

Ultimately, ensuring safety from touch and step voltage is an interdisciplinary challenge that requires the integration of power system analysis, geotechnical engineering, and protection system design. It is an exercise in managing potential differences, recognizing that safety is achieved not by eliminating voltage, but by controlling it with a thorough understanding of the physics of the fault, the physiology of the human body, and the robust application of established engineering principles.

Works cited

1. Touch and Step Voltage Calculations - EasyPower, https://www.easypower.com/resources/article/touch-and-step-voltage-calculations 2. What is Touch & Step Potential? Risk Reduction for Lightning Explained! - YouTube, https://www.youtube.com/watch?v=PhvrwHmKe_M 3. Step vs Touch Potentials: Electrical Shock Prevention Guide, https://electricalengineeringplanet.com/step-vs-touch-potentials-electrical-shock-prevention-guide/ 4. Step Potential Around Power Lines - Cornhusker PPD, https://cornhusker-power.com/safety/step-potential/ 5. Understanding Step and Touch Voltage: Safety Measures | ES Grounding, https://esgrounding.com/step-and-touch 6. Step and touch voltages. | Download Scientific Diagram - ResearchGate, https://www.researchgate.net/figure/Step-and-touch-voltages_fig1_331617113 7. Protection from Hazardous Step and Touch Potentials - The Hubbell Blog, https://blog.hubbell.com/en/hubbellpowersystems/hazardous-step-and-touch-potentials 8. Why does current flow through my body if I touch a hot wire?, https://electronics.stackexchange.com/questions/688639/why-does-current-flow-through-my-body-if-i-touch-a-hot-wire 9. Basic Electricity Safety - OSHA, https://www.osha.gov/sites/default/files/2019-04/Basic_Electricity_Materials.pdf 10. Question of how electricity flows through a body when shocked : r/AskElectricians - Reddit, https://www.reddit.com/r/AskElectricians/comments/1mjt8ut/question_of_how_electricity_flows_through_a_body/ 11. Earthing System Design in AC Substations: IEEE STD 80 Requirements, https://kingsmillindustries.com/earthing-system-design-in-ac-substations-ieee-std-80-requirements/ 12. Three main techniques for mitigating step and touch potential hazards | EEP, https://electrical-engineering-portal.com/mitigating-step-touch-potential-hazards 13. DESIGNING SAFE AND RELIABLE GROUNDING IN AC SUBSTATIONS WITH POOR SOIL RESISTIVITY: AN INTERPRETATION OF IEEE STD. 80, https://www.cablejoints.co.uk/upload/Designing-Safe-and-Reliable-Grounding-In-AC-Substations-With-Poor-Soil-Resistivity-By-IEEE.pdf 14. What is Step and Touch Potential?, https://stepandtouch.com/whatis/ 15. Reach Touch Voltages Explained - ELEK Software, https://elek.com/articles/reach-touch-voltages-for-safety/ 16. What is Step & Touch Potential? Definition & Explanation - Circuit ..., https://circuitglobe.com/step-and-touch-potential.html 17. Substation Grounding Basics: Step, Touch, and Transferred Voltages - Technical Articles, https://eepower.com/technical-articles/the-basics-of-substation-grounding-step-touch-and-transferred-voltages-part-2-of-3/ 18. Reducing the Risk of Step and Touch Potential - GreyMatters, https://greymattersglobal.com/step-and-touch-potential/ 19. Electrical Resistivity | US EPA, https://www.epa.gov/environmental-geophysics/electrical-resistivity 20. Step and Touch Potential Awareness:, https://stepandtouch.com/resources/step_and_touch_whitepaper.pdf 21. Shock Current Path | Electrical Safety | Electronics Textbook - All About Circuits, https://www.allaboutcircuits.com/textbook/direct-current/chpt-3/shock-current-path/ 22. ELI5: When is it safe for electric current to pass through the body, and when is it dangerous? : r/explainlikeimfive - Reddit, https://www.reddit.com/r/explainlikeimfive/comments/1dj11ox/eli5_when_is_it_safe_for_electric_current_to_pass/ 23. Step and touch voltage, https://www.dehn.cn/sites/default/files/media/files/pl014-e-0819_step_voltage_screen.pdf 24. Touch and Step Potential Testing - AEMC Instruments, https://www.aemc.com/userfiles/files/resources/applications/ground/APP-TouchStepPotential.pdf 25. Transferred Voltage Hazards - EasyPower, https://www.easypower.com/resources/article/transferred-voltage-hazards 26. Electrical Injuries - StatPearls - NCBI Bookshelf, https://www.ncbi.nlm.nih.gov/books/NBK448087/ 27. How much current will go through my body if I were to put my finger in an outlet?, https://physics.stackexchange.com/questions/555448/how-much-current-will-go-through-my-body-if-i-were-to-put-my-finger-in-an-outlet 28. Electrical injury - Wikipedia, https://en.wikipedia.org/wiki/Electrical_injury 29. The short-term and long-term effects of electric shock on the human body, https://burncenters.com/safety/the-short-term-and-long-term-effects-of-electric-shock-on-the-human-body/ 30. Safety Limit Calculations to IEEE and IEC Standards - ELEK Software, https://elek.com/articles/safety-limit-calculations-to-ieee-and-iec-standards/ 31. Conduction of Electrical Current to and Through the Human Body: A Review - PMC, https://pmc.ncbi.nlm.nih.gov/articles/PMC2763825/ 32. The effects of an electric shock on the human body - Hydro-Quebec, https://www.hydroquebec.com/safety/electric-shock/consequences-electric-shock.html 33. EFFECTS OF ELECTRICAL CURRENT IN THE HUMAN BODY Current Reaction - TUV Rheinland, https://www.tuv.com/content-media-files/usa/pdfs/1020-field-evaluation-service-(fes)-for-u.s.-and-canada/tuv_rheinland_02_effects_of_electrical_current_in_human_body.pdf 34. IEEE Standards Interpretation for IEEE Std 80™-1986 IEEE Guide for Safety in, https://standards.ieee.org/wp-content/uploads/import/documents/interpretations/80-1986_interp.pdf 35. Effects of the Changes in IEEE Std. 80 on the Design ... - Sestech.com, https://www.sestech.com/pdf/159_Changes%20in%20IEEE80.pdf 36. Grounding requirements for transformer substation according to IEEE Std 80-2000, https://zandz.com/en/news/20250211/grounding-requirements-for-transformer-substation-according-to-ieee-std-80-2000/ 37. A Method to Apply IEEE Std. 80 Safe Touch and Step Potentials to Relay Coordination | WPRC-Archives, https://wprcarchives.org/wp-content/uploads/2024/07/Lance-Grainger_Method-coordinate-IEEE-Std-80-to-relaying-G__2005.pdf 38. Design, Modeling, and Analysis of IEEE Std 80 Earth Grid Design Refinement Methods Using ETAP - MDPI, https://www.mdpi.com/2076-3417/13/13/7491 39. Grounding System Testing: Simplified Fall-of-Potential and Step-and-Touch Voltage Testing, https://netaworldjournal.org/2021/05/loganmerrill/industry-topics/grounding-system-testing-simplified-fall-of-potential-and-step-and-touch-voltage-testing/ 40. Touch & Step Potential | PDF | Power (Physics) | Manufactured Goods - Scribd, https://www.scribd.com/document/361431573/Touch-Step-Potential 41. Touch Voltage Calculations for LV Electrical Systems - ELEK Software, https://elek.com/articles/touch-voltage-calculations-for-lv-electrical-systems/ 42. Evaluating & Mitigating Transferred Voltage Hazards - EasyPower, https://www.easypower.com/resources/article/evaluating-transferred-voltage-hazards 43. GRADIENT CONTROL MAT DECOUPLING - Dairyland Electrical Industries, https://www.dairyland.com/applications/ac-voltage-mitigation/appguide_gcm/ 44. GROUNDING MAT 4X6' | Guillevin, https://www.guillevin.com/product/grounding-mat-4x6-hyd-6466gcm 45. Reducing Hazards of Step and Touch Potential, https://blog.hubbell.com/en/hubbellpowersystems/reducing-hazards-of-step-and-touch-potential 46. Ground-Gradient Control Mat - MVA Power!, https://mvasite.mvapower.com/index.php/substation/grounding/ground-gradient-control-mat 47. Gradient Control Mat Decoupling - Dairyland Electrical Industries, https://www.dairyland.com/applications/gradient-control-mat-decoupling/ 48. Gradient Control Mat - Cathtect USA, https://cathtectusa.com/product/gradient-control-mat/


Comments

Popular posts from this blog

Understanding LV Earthing Systems: TT, TN, and IT Explained

Understanding LV Earthing Systems: TT, TN, and IT Explained Earthing systems are crucial for electrical safety, protecting people and equipment from faults and shocks. In low-voltage (LV) installations, the IEC 60364 standard defines three main earthing systems:  TT, TN, and IT , each with distinct characteristics and applications. This blog post explains these systems, their subtypes, and key safety considerations, referencing the attached technical screenshots for clarity. 1. Classification of LV Earthing Systems Earthing systems are identified by a  two-letter code : First Letter: Neutral Connection T (Terra)  – Neutral is  directly earthed  at the transformer. I (Isolated)  – Neutral is  not earthed  or connected via high impedance (≥1000 Ω). Second Letter: Equipment Earthing T  – Frames are  locally earthed , independent of the neutral. N  – Frames are  connected to the neutral , which is earthed at the transformer. 2. Typ...

Understanding Short-Circuit Analysis with ETAP and the IEC 60909 Standard

U nderstanding Short-Circuit Analysis with ETAP and the IEC 60909 Standard Introduction: Short-circuit analysis is a critical aspect of electrical power system design and safety. It involves calculating the magnitude of fault currents to ensure the proper selection of protective devices and to verify that equipment can withstand fault conditions. This post will discuss how ETAP software performs short-circuit analysis in compliance with the IEC 60909 standard, a key standard in this field. Why is IEC 60909 Important? The IEC 60909 standard provides a globally recognized framework for calculating short-circuit currents in AC power systems. [Ref: IEC 60909-0:2016] Its importance stems from several factors: Ensuring Safety: Accurate short-circuit calculations, as mandated by IEC 60909, are crucial for selecting appropriately rated protective devices (circuit breakers, fuses) that can safely interrupt fault currents. [Ref: Short Circuit Analysis (IEC 60909 Standard) : Extent & Requir...

Understanding Short-Circuit Calculations in Electrical Systems

U nderstanding Short-Circuit Calculations in Electrical Systems Introduction: Short-circuit calculations are fundamental to the design, protection, and safety of electrical systems. Determining the magnitude of fault currents allows engineers to select appropriate protective devices (like circuit breakers and fuses), ensure equipment can withstand fault conditions, and ultimately safeguard personnel and property. This post will explore some of the key equations, formulas, and underlying principles involved in these crucial calculations. Key Concepts and Equations: When performing short-circuit calculations, several factors and formulas come into play. Here are some essential ones: Transformer Impedance: It's important to note that transformer impedance is often based on the transformer's self-ventilated rating (e.g., the OA base is used for ONAN/ONAF/OFAF transformers). Voltage Notation: Throughout these calculations, line-to-line voltage in kilovolts is represented as (kV)...